ELECTRICAL DESIGN CRITERIA (POWER AND COMUNICATION)
A- ELECTRICAL POWER & LIGHTING DESIGN CRITERIA
1. General
1.1 Introduction
This section describes the basic design
guidelines that will be used in preparing the electrical design and documents
for
The medical center is part of a campus with one infra-structure.
The campus shall have a main power supply from the Saudi Electricity Company SEC. For a campus of this size SEC usual builds a transformer station to transform power supply from 132 KV to 13.8 KV. SEC usually asks for a piece of LAND around 50x60m to put the transformers and equipment at that location.
The medical campus shall have its own
13.8 kV main substation to distribute the 13.8 kV power to all buildings in the
campus. It is recommended to keep the low voltage as a unified voltage in all
buildings 380/220 V 3phase, 60 Hz. This is in line with the trend in
1.2 Scope of Work
The electrical systems for this building shall consist of the following items including all the necessary raceway:
The communication, security and control systems are covered in section "B- COMUNICATION, SECURITY AND CONTROL" of this report
1.3 Codes and Design Standard
The SAUDI ARABIAN STANDARD ORGANIZATION
(SASO) is the official standard organization of
Based on the above Saudi National Standard Policy; All the Electrical systems shall follow the following main standards
BS British Standard including IEE Wiring regulation
NEC, NFPA and other American standards
All electrical products specified for this building shall be specified according to one of the following standards as per sequence:
SASO Saudi Arabian Standard Organization
IEC International Electrical Commission
Other Europeans standards like EN, BS, DIN, etc.
Other American Standards Like ANSI, NEMA, ASTM and IEEE
The electrical products used in this building shall be tested and approved to meet the applicable standards by one of the independent test laboratories (or approving agencies) including: SASO, IEC, BS, ASTA, KEMA or UL or similar agencies.
Following specialized standards shall be used:
1.4 Environmental Conditions
The ambient temperature to be used for calculation purposes is tabulated as follows:
Description |
Ambient Temperature For Derating Purposes Deg. C |
CABLES Directly buried or duct bank (min. 600 mm below grade) In conduit in ventilated area below grade 828b19i In conduit exposed to out side air or directly in air In conduit in conditioned space In cable tray or conduits above conditioned space |
|
EQUIPMENT Well-ventilated building (no air condition ) Air condition for equipment, substation, etc. Installed outdoors Air-conditioned for comfort, offices, etc. |
|
1.5 Utilization Voltage
The following table indicates the nominal system and standards utilization voltages for particular items of electrical network.
Service |
System Voltage Volts |
Remarks |
Medium Voltage Supply |
|
Three phase |
Low Voltage Supply |
|
Three Phase |
A/C System |
|
Three Phase |
Single Phase Motors |
|
Single Phase |
Indoor Lighting |
|
Single Phase |
Outdoor Lighting |
|
Single Phase |
General Purpose Outlets |
|
Single Phase |
Power Outlets |
|
Single Phase |
1.6 Voltage Drop
For calculation of voltage drop; the following rules shall be used: A maximum Total of 2% from the main supply intake position "transformer" to "Main Distribution Board" MDB.
A maximum Total of 3% from the Main Distribution Panel "MDP" to the farthest point of use shall be used.
A maximum Total of 5% from the main supply intake position "transformer" to the farthest point of use shall not be exceeded.
1.7 Branch Circuits
The design shall be based upon the use of copper conductors of a minimum of 4 mm2.
16A and 20A (Ampere Trip) Circuit Breakers will be used for wiring of power and lighting branch circuits. Most of the circuit will use 20A, but for small loads like in guard house or similar cases, the 16 A can be used.
With derating for inside panel temperature, the 20A nominal Circuit breaker is only 17 A.
By allowing 25% spare the 20A nominal circuit breaker shall be loaded to 13.6A
Separate lighting and power/receptacle circuits.
20 percent spare ways will be provided in lighting and/or receptacle panel boards.
1.8 Socket Outlets
General-purpose Receptacle outlets will be provided as required and shall be limited to eight per branch circuit. The general purpose receptacle shall be as per applicable standard SASO (13A). The general-purpose receptacles are in addition to the special purpose and dedicated outlets for specific equipment such as outlets for computers, office equipment and other
Circuit loading shall be estimated on the basis of 180 VA for each outlet, unless specific conditions necessitate other loading.
All sockets outlets in wet areas, outside areas and kitchen shall be protected with earth leakage circuit breakers ELCB. The sockets in the outside shall also be weather-proof
Receptacle and plug configurations for the specified number of poles as per code and client requirement,
Each Local Area Network (LAN) workstation telecommunication outlet will be provided with a dedicated well-defined adjacent duplex receptacle on an independent single phase (220 volt) circuit having not more than four duplex receptacles and a non-shared neutral. Circuit Loading for LAN workstation shall be calculated based on 500 VA for each outlet. The demand factor for workstation is 1.
Fax, copy equipment and laser printers will be provided with independent circuits.
1.9 Utilities Interface
This whole campus shall be connected to Saudi Electricity Company (SEC) power supply. Preliminary coordination with SEC shall be arranged during the design stage. Final and detail coordination shall be arranged by the contractor at the beginning of construction stage. The building owner shall take part in the coordination. Power supply Contract can only be signed between SEC and building owner.
2. Electrical Systems and Equipment
2.1 Normal Power Supply and Distribution
Electrical supply shall be provided from the Saudi Electricity Company SEC at 13.8 kV via a transformer substation (132/13.8 kV). A space shall be allowed for SEC at the boundary along a main street (two streets). All the issue concerning the power supply shall be closely coordinated and agreed with SEC during the design stage.
A 13.8 distribution switchgear, 13.8 kV cable network, transformers and complete low voltage distribution shall be designed as part of medical center property. The maintenance of these equipments shall be by the medical center maintenance staff (or contractor). This system will give the medical center flexibility to modify and add any building at any time without asking SEC. Usually SEC charge the cost of the transformer substation on the project.
2.2 Electrical Load Requirement
The attached spread sheet indicates the preliminary load estimation.
The loads indicated are preliminary estimation for space allocation of electrical equipment and shall be adjusted according to the actual loads when it becomes available.
2.3 Transformers and RMU
Transformers of this project shall be both oil type for chillers and external areas and dry type resin encapsulated for inside the building.
The work shall include transformers and Medium Voltage Compartment Ring main units. The RMU shall be SF6 insulated, non-extensible with two- (2) load break switches and one transformer circuit breaker. All other auxiliary component shall be included. Ratings shall be as required and indicated on the drawings.
Transformer Specifications for external oil type
Type Distribution (120º C rise minimum oil type)
Ventilation Natural cooling
Phase Three (3)
Temperature 65 deg c rise over a 50 deg c ambient
Frequency 60 hertz
Bil 95 kV
Taps Two 2-1/2% primary above and two 2-1/2 % primary below
Core Five - legged
Primary voltage 13,800V
Secondary voltage as indicated on drawings
For 380/220v system transformer shall have 400/231V at NO-LOAD
KVA ratings as required in the drawings
Impedance's 5.75 %
Noise level shall not exceed 67 db
Winding connections Delta - Star, Vector Group DYII
Similar modified specification for dry type shall be used
2.4 Essential (Standby) Power Supply
Standby generators will be installed to provide power supplies for the essential loads in case the main power supply fails.
A generator room will be provided in a suitable location and shall be coordinated with the architect.
Diesel Engine driven generator sets shall be provided as standby power. Automatic transfer switch shall automatically start the generator.
For the medical center a complete diesel power generation plant with synchronization. The standby generation is about 60 to 70% of normal load
The following are the minimum emergency loads to be connected to standby generator:
2.5 Building Electrical Distribution
Power supply for the building shall be split into essential and non essential loads. The essential load will be connected to the standby generators. For hospital in particular we shall use 3 load categories:
Emergency system including:
o Critical Load
o life Safety Loads
Essential Equipment
Standard (Nonessential Loads)
From the low voltage Switchgear room service cables (feeders) shall be run to the main loads and sub-distribution panels and to the branch circuit panels.
Bus bar trunking (busway) shall be used in the riser to reduce space requirement and increase reliability.
Inside the building cables shall be installed in metal cable tray and EMT conduit.
Wiring to final branch circuits shall run in small busway, EMT conduit.
2.6 Panel Boards and Motor Control
Main Distribution Boards (MDB), Distribution Boards (DB), power and lighting panel boards shall be circuit breaker equipped, dead front construction, complying with SASO 1609/ IEC 60439. Circuit breaker shall be molded case bolted type. Multi-pole breakers shall have common trip with single operating handle.
All distribution, power and lighting board shall be of Type Tested Assemblies (TTA) as defined in SASO 1609 / IEC 439.
Lighting and appliance branch circuit panel boards shall be circuit breaker equipped, complying with minimum short circuit and interrupting capacity of 10% more than the calculated maximum short circuit on the protected circuit and shall not be less than 10 kA. Breaker trip ratings shall be as required.
Motor control shall comply with requirements of SASO/ IEC. All items shall be for 60 Hz.
Branch circuit panel boards shall be of the circuit breaker type. Feeder, distribution, and sub-station panel boards shall be current limiting circuit breaker. A main circuit breaker or disconnect shall be provided on all panel boards when two or more panel boards are supplied from the same feeder. All panel boards shall be provided with insulated neutral terminals and equipment grounding terminals.
Supplying small single-phase loads from power and distribution panels shall be avoided. Large three phase loads shall not be fed from lighting panels. Lighting and small panel boards may be combined for small facilities, but shall generally be segregated for larger facilities.
The location of panel boards shall be coordinated with architectural drawings to assure cabinet mounting is correct for the location and wall type. Panel location shall provide for economical distribution of branch circuit conductors and minimum voltage drop.
Spare circuits and spaces in power and distribution panel boards shall be provided at 25 percent of active circuits. The spare circuits shall be included when applying demand loads for feeder, panel, and transformer sizing. For panel boards recessed in finished wall spaces, spare circuits shall be called out to be provided from a panel boards to overhead accessible areas for the spare circuits.
All electrical equipment, including switchboards, panel boards, controllers, metering cabinets, transformers and special equipment shall be housed within enclosures with the correct IP rating.
ISOLATED POWER Panel Boards:
Isolated Power panel boards shall be installed for critical medical areas and equipment like OR, ICU, CCU and any area where medical equipment are attached to the human body.
The isolated power panel boards are specially designed panel for this purpose and shall include as minimum:
Shielded low-leakage isolating transformer, specifically manufactured for the use in hospital isolated systems
Line isolating monitor (LIM)
Circuit breakers
Remote alarm indicator.
2.7 Switches, Circuit Breakers and Fuses
Safety Switches
Safety switches shall be according to IEC 60947-3. All Motor safety switches shall be rated for category AC-3 (motor duty) according to IEC 60947-3.
The switches of 60 ampere and below shall be general-purpose, with pilot light if required, and ratings as indicated on the drawings. Safety switches above 60 A shall be as follows:
Molded Case Circuit Breakers (MCB and MCCB)
AIR CIRCUIT BREAKERS (POWER CIRCUIT BREAKERS)
Ordinary Low-Voltage Fuses
Cartridge types, one - time use and shall be according to IEC. They shall have markings, or adjacent to them an identification of the type of links to be used.
Motor Disconnect Means
Each motor shall be provided with a heavy - duty disconnection means. The rating shall be for category AC-3 (motors) as per IEC 60947-3.
2.8 Wires and Cables
Branch circuit wires shall consist of moisture and heat resistant thermoplastic (PVC), 85 Deg C, 750 V copper conductors according to SASO 55 and IEC 228. Feeders for indoor and outdoor installations shall be XLPE, 90 Deg c, 1000 v copper conductor multi-core or single-core type.
All wires 2.5 mm2 and above shall be stranded conductors. Stranding shall be circular none compacted according to IEC 228 class 2, or approved equivalent.
The wiring will be installed in a system of trunking, trays and conduits.
A separate green/yellow colored grounding conductor shall be used throughout to insure grounding continuity.
Aluminum conductors will not be used in the construction of this facility only copper conductors will be used.
Feeder circuits shall be run in cable tray, rigid conduit, intermediate metal conduit, or electrical metallic tubing except where large loads justify the use of enclosed bus bars.
Feeders shall be derated for high ambient temperature where required. General routing of main feeders shall be shown on the drawings where required for purposes of construction.
Wiring methods and materials shall be those recognized by the SASO, IEC, BS and NEC, except as modified below. All interior power, lighting, and line voltage control conductors shall be run in raceways, except where cable tray systems are used. Low voltage and temperature control wiring shall be encased in conduit where the run is exposed.
MV cables shall be 15 kV 3 cores with armor if installed direct in ground. For installation in duct-bank no armor is required.
2.9 Man-holes/Hand-holes
If required, man-holes/Han-dholes shall be of the cast-in-place type. Straight runs between manholes shall not exceed 150 meters. Shorter distances will be used when change in direction is required. Hand-holes will be mainly used for communication systems.
2.10 Earthing and Safety
The Earthing system shall be according to SASO 981, 982, 983, 984, etc. equivalent to different parts of IEC 60364 Part 1, 4, 5, 6 and 7 (all parts)
SASO
IEC 60364-5-54 is particularly for earthing. Earthing wires shall be sized accordingly.
Earthing system shall be TN-S according to SASO 981 equivalent to IEC 60364-1
For ICU, CCU Operation Theater an isolated Power system shall be used to increase the reliability of the system
Ground cables: soft drawn, bare stranded copper wire, tinned, or insulated stranded copper wire conductor cables. The minimum cross-sectional area of protective conductor shall be according to table 54.3 of IEC 60364-5-54 and in no case smaller than 2.5 mm2
Ground rods: copper cladded steel rod or copper alloy, 19-mm diameter, furnished in 3.00-m lengths.
A separate grounding conductor will be provided for each circuit in all building lighting and power conduits.
2.11 Conduits and Raceways
Interior Raceways
Exterior Raceways
2.12 Lighting
2.12.1 Interior Lighting System
The interior lighting of the main public area shall be emphasized to create special architectural effect and attraction. The architect shall develop the main concept of the interior (decorative) lighting
For offices and general areas; energy efficient design considerations shall include use of efficient lamps and luminaries.
The most energy efficient lamps and fixtures shall be used.
Fluorescent lamps will be cool white, energy saving types (T5) 16 mm diameter. These lamps are the most modern and energy efficient in the market.
Louvers shall energy saving aluminum louvers
Electronic Control gear (ECG) with dimmable function shall be used.
The buildings are designed by the architect to make use of the natural day lighting. This concept requires the use of some control to reduce or switch off the lighting luminaries based on the day lighting available. The energy saving comes from this control.
That is why a lighting control system like EIB (European Intelligent Bus) is recommended in connection of day light sensors, presence sensor and dimmable ECG shall be used.
Lighting fixtures will generally be rated for 220-Volt operation
2.12.2 Interior Illumination Levels
For offices, class rooms, laboratories and service areas; illumination level shall follow the recommendation of IES Illuminating Engineering Society Lighting Handbook 8th edition.
The following lighting criteria table has been selected from the tables of IES for the particular areas.
Lighting Criteria table |
|||
The illumination level (LUX) in this table represents average illumination. The calculation shall target these values (+) or (-) 10%. Architectural symmetry and interior designer requirement shall be considered |
|||
ROOM (AREA) DESCRIPTION |
LUX |
Remarks |
|
Lobby |
|
|
|
Corridor |
|
|
|
Staff Rooms |
|
|
|
Staff office |
|
|
|
Rest or waiting room |
|
|
|
Toilet |
|
|
|
Change |
|
|
|
Entrance |
|
|
|
Prayer room |
|
|
|
Electrical room |
|
|
|
Communication room |
|
|
|
Meeting room |
|
|
|
Reception |
|
|
|
Class room |
|
|
|
Janitor |
|
|
|
Toilet/shower |
|
|
|
Training |
|
|
|
Lecturer |
|
|
|
Filling/Printing |
|
|
|
Disinfector |
|
|
|
Parking |
|
|
|
Transformer room |
|
|
|
MEDICAL AREAS |
|
|
|
Operation room |
|
|
|
Recovery room |
|
|
|
Treatment room |
|
|
|
Medical Library |
|
|
|
Laboratory |
|
|
|
Examination |
|
|
|
Consultant room |
|
|
|
Intensive Care |
|
|
|
Patient room |
|
|
|
X-Ray Film handling |
|
|
|
Pharmacy |
|
|
|
Medical Preparation |
|
|
|
Intensive Care |
|
|
|
Scanners |
|
|
|
Deputy Doc |
|
|
|
Medical work shop |
|
|
|
Ventilator |
|
|
|
Sterilizers |
|
|
|
Blood bank |
|
|
|
Auditorium |
|
|
|
Store |
|
|
|
VIP Treatment |
|
|
|
External Lighting |
|||
Roads major, collector, local |
|
HPS |
|
Parking (covered) |
|
Fluorescent |
|
External parking |
|
HPS |
|
2.12.3 Street and Area Lighting
External Lighting (road and area lighting) will be coordinated with the architect and landscape design. Lighting control will be achieved by orbit timer, photoelectric cells and contactactors. Manual option shall be provided. EIB shall be used for control
3. Special Systems
3.1 Lightning Protection System
The work under this section shall consist of furnishing and installation of a complete lightning protection system for the building of the air terminal type.
Air terminal type material and components will comply with BS 6651, in accordance with published product information. The system will be provided with air termination network, bonding plates, conductors, connectors, conductor straps, fasteners, grounding plates, grounding rods, rod clamps, splices and other components required for a complete system. High conductivity annealed copper tape 20 * 3 mm with rounded edges with bases. Length as indicated on the drawings.
Conductors: High conductivity annealed bare stranded copper wires. Length and size as indicated on the drawings. Roof conductors coursed along masonry surfaces shall be secured with copper masonry fasteners. Conductors coursed on the roof deck shall be secured with adhesive cable holders spaced as shown on drawings. The download conductors shall be concealed and routed down in cavity walls or in PVC conduits concealed in concrete walls.
Ground Rods: Each down conductor shall terminate at a ground rod, which is part of the common building ground grid. Ground rods shall be 20-mm diameter (3/4"), 3.00-meter long copperbond steel rod.
3.2 Uninterruptible Power Supply (UPS)
UPS room shall be provided in the area of server and communication rooms. UPS shall be used to serve the critical hospital areas like:
Operating rooms
ICU room
CCU rooms
The UPS shall be selected with the latest
technology available to reduce the harmonic distortion and improve power
factor. UPS shall be On-Line double conversion including Rectifier,
The UPS shall meet the IEC 62040-X all parts, in addition to the following minimum requirements:
UPS shall be sized to cover the following items:
BUILDING MANAGEMENT SYSTEM "BMS"
4. Basis for Electrical Design and Calculations
4.1 General
Calculation shall be performed based on the standards and codes indicated in the section of codes and design standard.
The following standards in particular shall be observed
4.2 Programs for Calculation
The following programs shall be used for calculation:
4.3 Load estimation and calculation
All the loads in the building shall be tabulated in the panel load schedules.
The following table of loads shall be used as a guideline.
It shall be noted that all panel boards, Main Distribution Board (MDB), Distribution Board (DB), Circuit Breakers and cables shall be selected with rating to allow for 20% spare and future growth. This 20% spare shall not be shown as a load in the panels but shall be considered when sizing the cables and selecting the circuit breakers. The sizes of cables and breakers shall be selected to carry the maximum demand loads multiplied by a factor of 1.25. This allows 20% spare.
Table for Equipment Loads and Power Factors
Note: This table shall be used only in case the exact manufacturer data are not available. If manufacturer selection and power requirement are available, then use power as per catalogue |
||
Type pf load |
Demand LOAD VA |
PF |
LAMPS |
|
|
Incandescent and Halogen Lighting Fixtures |
Lamp Wattagex1 |
|
Fluorescent Fixture with magnetic Ballast |
Lamp Wattagex1.4 |
|
Fluorescent Fixture with HF electronic Ballast |
Lamp Wattagex1.1 |
|
Mercury Vapors Lamp |
Lamp Wattagex1.5 |
|
Metal Halide lamp |
Lamp Wattagex1.5 |
|
High and Low pressure sodium lamp |
Lamp Wattagex1.5 |
|
Socket Outlets |
|
|
General Socket Outlets |
|
|
Power Outlets for specific equipment |
Manufacturer Catalog |
|
Office Equipment |
|
|
COPY MACHINE |
|
|
PRINTER |
|
|
FAX MACHINE |
|
|
PC station (CPU+ Monitor) |
|
|
LASER PLOTTER (FOR DRAWINGS) |
|
|
Scanner |
|
|
Mechanical Equipment |
|
|
Pumps and fans |
Manufacturer Catalog |
|
Electric Water Heater |
Manufacturer Catalog |
|
HVAC equipment (Chillers, AHU, PACKAGE) |
Manufacturer Catalogue |
|
4.4 Demand loads
Demand Factor for this building shall be estimated based on the following
Table for Demand Load Factors
Type of load |
Demand Factor |
Lighting Load |
|
General Socket outlets |
|
Computer Station Outlets |
1 (based on 500VA Per a station outlet) |
HVAC equipment |
|
Small kitchen equipment (if more than 6) |
|
|
|
B- COMUNICATION, SECURITY AND CONTROL
1- General
1.1 Introduction
This section describes the basic design guidelines that will be used in preparing the communication, security and control design and documents for this project.
A modern system for communication, security and control shall be designed according to the latest trend in communication. All the main equipment, controllers and systems shall have the capability to integrate with the other systems using open protocols and TCP/IP LAN
1.2 Scope of Work
The communication systems for this building shall consist of the following items including all the necessary raceway:
Note that UPS has been included as part of the power and lighting report.
1.3 Codes and Design Standard
Fire Alarm System
Telecommunications
2. Communication System
The building shall have a complete LAN system based on fiber optic and UTP CAT 6a cables using TCP/IP. All the communication system shall be based on the latest approved modern technologies available in the market.
2.1 Generic Cabling For Premises (Structured Cabling)
A complete structured cabling system shall be designed based on ISO/IEC 11801 2002 and EIA/TIA 568A, B. The system shall be universal and support telephone, data, video and others. The system shall support Ethernet as defined by IEEE 802.3 standard and shall be open to any new applications that require an ISO/IEC 11801.
Structured cabling system shall be installed, tested certified and guaranteed by an authorized supplier/contractor. The warranty shall provide performance guarantee for 20 years.
The system shall support 10 Giga speed (CAT 6A) component, and shall be configured in star configuration with full redundancy using fiber optic as back bone and UTP horizontal cable to each communication outlets
The system shall include, but not limited to:
All the component of the structured cabling system shall meet the requirement of CAT 6a (E) as per ISO/IEC 11801 and EIA/TIA 568A, B. and shall meet the following minimum requirement:
Horizontal Cabling
The horizontal cabling shall be 4 pairs Unshielded Twisted Pairs (UTP) category 6a.
The cable shall have solid conductor of 0.55mm diameter. Cable shall be PVC insulated and twisted and shall be LSZH (low smoke Zero Halogen). Performance and twisting shall be guaranteed to meet or exceed the ISO/IEC 11801 standard
Each Telecommunication outlet shall have two cables in general
Fiber optic cables can be used for the horizontal cabling if the distances between telecommunication outlet and patch panel communication cabinet
Telecommunication Outlets (Faceplates)
As recommended by the ISO/IEC 11801 standard at least 2 RJ45 outlets per Telecommunication outlet
Telecommunication Outlet shall follow the furniture layout i.e. one telecommunication outlet for each workstation or for each 10 m2 of usable workspace where there is no recommendation or furniture layout.
Every office, clinic, patient room, class room, lab shall have a minimum of one Telecommunication outlet (one faceplate with 2 RJ45 outlets)
Special communication requirement shall follow the medical equipment liayout
Telecommunication outlets shall be provided at proper location to allow the installation of Wireless Access Point, so that users can use their laptops and wireless devices to access information from any location in the hospital
The wall-mounted faceplate shall match the wiring devices finishes and shape and it shall accept modular type RJ45 outlets (2 or 4 as required)
Patch Panels
Copper patch panels must have 19" to fit in the standard 19" cabinet, rack or bay. Patch panels must be modular, and have RJ45 connectors. A typical 1HU high patch panel shall have 24 port modular snap-in RJ45 connectors
Performance and specification shall meet or exceed CAT 6a ISO/IEC 11801
The optical fiber patch panel must have 19" to fit in the standard 19" cabinet, rack or bay. The patch panel shall support the ST or SC connector type.
All patch panels, patch cord and accessories shall be CAT 6a rated.
Backbone Cabling
The backbone cabling is used to connect distribution rooms or cabinets together. Tight-buffered multimode fiber optic cables 50/125 are usually used for backbone cabling. The cable shall support gigabit Ethernet. A minimum of 6 fibers shall be used for backbone cabling. Cable performance and distances covered shall meet or exceed the standard requirement. Cables shall have LSZH (low smoke Zero Halogen) sheathing material that does not give off toxic fumes in case of fire.
Cables in duct bank; outside the building; shall be dry construction i.e. with no gel content. The jacket material shall be waterproof LSZH
Single mode fiber optic cables shall be used to cover long distances in the
Voice Cabling
To connect the PABX to the different floor distributor, the voice cabling between the PABX, MDF and floor distributor shall be multi-pair cables.
Raceway
The generic structured cabling system shall be installed using a system of hot dip galvanized cable tray and light duty metallic conduit (EMT) or other accepted conduit system.
2.2 Software and server
The entire active component like switches, routers, servers, computer and software are not in the scope of work of this contract.
The scope covers only the infra-structure for the DATA networks as defined above and as per standard ISO/IEC 11801 2002 and EIA/TIA 568A, B
2.3 TELEPHONE SYSTEM (IP-PBX)
A complete Private Automatic Branch Exchange (IP-PBX) shall be designed for this building. The IP-PBX shall be microprocessor based modular type. PABX shall allow the use of IP-telephones, SIP phones, Digital ISDN and analogue lines.
The PABX system shall include, but not limited to:
The capacity of the PABX shall cover the entire telephone requirement as in the layout plan plus 20% spare for future expansions.
Number of external line for the building shall be estimated as 15% of the PBX size to cover the entire requirement.
It should be noted the telephone wiring from the communication room to the each desktop will be the same CAT6 cables as described in the structure cabling.
Back bone cabling for the telephone from the PABX to each floor can be multi core CAT3 telephone cables. This system allows the use of standard type of telephones and at the same time allows future upgrade to IP-phones and complete IP telephony solution
2.4 Master Antenna Television Systems (MATV)
Inside the building, a completely wired MATV system will be provided. The MATV shall include, but not limited to, the following component:
The location for the TV outlets shall include; patient rooms, waiting areas, managers and directors offices, rest areas and any other location required by client.
2.5 Public Address
The PA shall provide paging, emergency broadcast, and praying announcement. A remote microphone shall be used for emergency broadcasts on group or all speaker systems. Emergency broadcasts shall have priority over other broadcasts.
The PA shall be combined with the voice evacuation system without violating the code.
The system will be provided in corridors and waiting areas, with the main control panel installed within the security room.
The system shall consist of, but not limited to, the following:
Equipment and components shall conform to the requirements of the applicable standard. All electronic components shall comply with the appropriate standards of manufacturer country. Electronic components shall be of types and ratings commonly available from stock of established commercial distributors.
The system will have the following features:
2.6 Clock System
The system shall consist of, but not limited to, the following
2.7 Fire Alarm System
Automatic fire detection is required by Civil Defense Department recommendation. The system shall be as following:
3. Security Systems
3.1 Closed Circuit Television Surveillance (CCTV
A modern Digital CCTV system shall be installed for this building
The Digital Video Recorder (DVR) of the building shall record the cameras based on program and events.
The following areas shall be monitored:
The system shall consist of, but not limited to, the following
The camera specified here shall be designed to meet needs of industrial applications. Two types of cameras for outside and inside shall be specified.
The outside camera shall be housed in dust tight enclosure with removable covers. The lens shall be auto iris totally enclosed within the housing and shall have a shatter proof front window.
Camera shall have 1/3 CCD with digital signal processor (DSP)
Camera shall have minimum resolution of 480 TV lines
The monitors shall be racks mounted design. It shall be fully solid state except for the cathode ray tube; controls shall include brightness, contrast, vertical and horizontal hold.
The digital video
recorders (DVR) shall be software based and shall use open system architecture.
It shall use industry standard PC technology with
The DVR shall support 2 monitors and a control monitor
The DVR HARD DISK shall have a capacity sufficient to record all CAMERAS at standard recording rate and sequence for 3 months.
Coaxial shielded copper cables running in 25-mm conduit between equipment.
3.2 Access Control System
The high security areas shall have secure doors with electronic card reader to limit the access to theses areas only for designated personnel.
The Access control system shall include, but not limited to, the following:
All the access control system shall be controlled and monitored from a master control station and shall be integrated with other security system (CCTV).
System shall have the ability to integrate with other security system using open protocol and TCP/IP LAN to make one integrated system
4. Control
4.1 Building Management System (BMS
A BMS system is needed to control and monitor the AIRCONDITION A/C equipment and other equipment
Following equipment shall be fully controlled by BMS:
Following equipment shall be fully monitored by BMS and integrated with the BMS:
5. Nurse Call System
6. Digital Discussion & Conference System.
Central Control equipment ( CCU )
PC Control
Software Module
Information Distribution Equipment
Simultaneous Interpretation and language distribution
|