Documente online.
Zona de administrare documente. Fisierele tale
Am uitat parola x Creaza cont nou
 HomeExploreaza
upload
Upload




MEMORIU TEHNIC INSTALATII HIDROTEHNICE gospodarie de apa potabila si incendiu interior FAZA PT

Arhitectura constructii


MEMORIU TEHNIC INSTALATII HIDROTEHNICE



gospodarie de apa potabila si incendiu interior

FAZA PT

I.   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;    DATE GENERALE

Denumirea obiectivului:

Reabilitare ansamblu scolar "Liceul Kretulescu"

II. DATE SPECIFICE

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   Modul de incadrare in planul de urbanism

Ansamblul scolar "Liceul Kretulescu" compus din trei corpuri este situat in Bucuresti, ----- ----- ------ -, Sector 3, BUCURESTI

Cladirile sunt structurate pe parter +3 etaje (sali de clase, cabinete, grupuri sanitare, etc.)

Exista si o sala de sport cu dusuri si vestiare.

Descrierea lucrarilor

2.1.   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p; Date functionale

Regim de inaltime

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   Hmax=12mp

Structura de rezistenta este din caramida eficienta (BCA) ----- cm

Suprafata construita imobil  - -------- mp

Suprafata desfasurata imobil - -------- mp

Volum imobil  - --------- mc

DESCRIEREA LUCRARILOR DE INSTALATII

Prezenta documentatie trateaza instalatiile hidrotehnice, respectiv reabilitarea gospodariei de apa cu scop de ridicare a presiunii apei in instalatia interioara de apa potabila de consum menajer si incendiu interior aferenta celor trei corpuri de cladire.

Aceasta se gaseste situata in corpul "A".

3. NOMINALIZAREA PLANSELOR CARE GUVERNEAZĂ PROIECTUL

1.   &nbs 24124p1514y p;   &nbs 24124p1514y p;    Planuri si relevee de arhitectura

PREZENTAREA LUCRĂRII, CARACTERISTICI TEHNICE SI DE CALITATE

4.1. DESCRIEREA INSTALATIILOR

4.1.1. ALIMENTAREA CU APA

4.1.1.1 Situatia existenta

La limita de proprietate a ansamblului se afla reteaua oraseneasca de apa potabila, pe soseaua -----------. Racordul aferent intregului ansamblu eate in functiune, ca urmare are toate avizele de functionare.

4.1.1.2. Situatia propusa

Consumul menajer

Sursa de apa potabila a investitiei o va constitui reteaua oraseneasca.

Pe racordul de la retea, la limita de proprietate, exista un camin de vizitare (dimensiuni 1.0x1.0x1.20m) cu vanele de sectionare si apometrul. Racordul este realizat cu conducta din polietilena de inalta densitate PEHD 63.

Racordul alimenteaza un rezervor de stocaj apa potabila cu o capacitate de 15mc, reprezentind rezerva intangibila pentru alimentarea hidrantilor interiori de incendiu + rezerva de apa potabila menajera aferenta ansamblului.

Rezervorul tampon are drept scop preluarea neuniformitatilor de consum.

Din acest rezervor tampon vor aspira:

·   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;  un grup de pompare, cu variator de turatie, care va asigura presiunea necesara bunei functionari a urmatorilor consumatori :

- obiectele sanitare din cladiri

- sistemul de preparare apa calda pentru a.c.m.

- racordul la centrala termica

·   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;  un grup de pompare care va asigura presiunea necesara bunei functionari a instalatiei de hidranti interiori

Rezervorul si cele doua grupuri de pompare se vor monta intr-un spatiu tehnic amenajat in corpului A.

Pentru asigurarea unei garantii a potabilitatii apei s-au montat in aval si amonte de rezervorul tampon filtre care elimina suspensiile posibile cat si urmele de substante organice si de eventuale mirosuri reziduale.

Din statia de pompare, apa rece va merge la consumatori.

Distributia apei reci pentru consumul menajer in cladire fiind comuna cu cea de incendiu interior se va realiza, cu teava din otel zincat f21/2".

Apa pentru stingerea unui eventual incendiu

Incendiu interior

Cf. STAS 1478/90 tabelul 5 si Normativului NP086/2005 art. 4.1 si Anexa 3 pentru cladiri cu sali aglomerate, volumul cladirii mai mic de 25000mc, se impune stingerea unui eventual incendiu cu hidranti interiori cu un debit de Qii = 2.5 l/s si 1 jet in functiune simultana.

Debitul total va fi de 2.5l/s si va fi asigurat pentru 10 minute de functionare.

Incendiu exterior

Conform NP086/2005 pentru constructii de invatamint cu mai mult de doua nivele se impune stingerea unui eventual incendiu cu hidranti exteriori. Pentru determinarea debitului, in anexa nr. 8 a aceluiasi normativ, ptr. cladiri cu gradul de rezistenta la foc "II" si volumul cladirii sub ----------mc se impune stingerea unui eventual incendiu cu hidranti exteriori cu un debit de Qie = ----- l/s.

Debitul va fi asigurat pentru 3 ore de functionare, si va fi asigurat de reteaua de hidranti oraseneasca.

5. BREVIAR DE CALCUL

5.1. Debite de apa rece de consum menajer

Cladire cu destinatie institutie de invatamint: grad maxim de ocupare 1200 persoane

Consumatori:

1.   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;    Sali de clasa si laboratoare

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  3dusuri

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  78 lavoare

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  93 vase WC

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  20 pisoare

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  3 robineti dublu serviciu ˝"

Debit de calcul q = a x bx c x E (l/s) cf. (STAS 1478- 90, tabel 6, tabel 7, tabel 8 )

q = a x bx c x E (l/s) a = 0.15 b = 1 c = 1.8

E = E1 + E2

E1 = 30.30

E2 = 55

E =85.30 E = 12

Rezulta:

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;    apa potabila rece : qar = 2.50 l/s

Echipament gospodarie de apa pentru consum menajer+incendiu interior

Grupul de pompare pentru consum menajer

Consider consumul menajer maxim

q menajer = 2.50 l/s = 9 mc/h

Hnec = Hu + Hg + H retea = 10 + 12+ 10 = 32 mCA

Se propune un grup de pompare cu variator de turatie compus din 1 pompa active + 1 pompa rezerva cu caracteristicile:

Dgp=1x9mc/h+1x9mc/h;

Hp = 32 ÷ 50 mCA

Grupul de pompare pentru incendiu int.

qiint =2.50 l/s

Debitul pompei pentru incendiu este debitul de incendiu+debitul menajer:

Dgp = 5/s=18 mc/h;

Se propune un grup de pompare compus din 1pompa activa + 1 pompa rezerva cu caracteristicile:

Dgp =1x18 mc/h+1x18 mc/h

Hgp = 32m CA

5.2. Necesarurile zilnice si orare de apa rece si calda

5.2.1 Apa pentru consum menajer, spalari,stropit spatii verzi:

Se va determina pe baza necesarurilor specifice de apa rece si calda, conform

STAS 1478-90

Numarul total maxim de persoane din cladire este:

·   &nbs 24124p1514y p;    1250 (elevi+profesori)

1250 elevi x 20l/elev, zi =25000l/zi

·   &nbs 24124p1514y p;    44 personal administrativ din care:

24ingijitoare x 50l/ pers. Schimb = 1200 l/zi

4 persoane intretinere x 60l/pers.schimb = 240 l/zi

16persoane TESA x 20l/pers.schimb = 320 l/zi

·   &nbs 24124p1514y p;    100 elevi sala sport

100 elevi x 50l/elev, zi = 5000l/zi

Qzi med =31760l/zi

Apa pentru stropit spatii verzi

Cf. STAS 1343 -1/95, pct. 2.3.2. se considera 25 l/mp la 2 saptamani.

Qs = 1,80 l/zi mp x 8000mp = 14400l/zi=14,40 mc/zi.

Debitele necesare de apa rece

·   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;    Debitul mediu zilnic de apa rece:

Nxqs 31760

Qzimed=---------- = ----------- = 31.76 mc/zi

1000 1000

·   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;    Debitul maxim zilnic de apa rece:

Qzimax= KzixKp/1000 x Qzimed =1,15x1.08 /1000x32 = 39.75 mc/zi

·   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;   &nbs 24124p1514y p;    Debitul orar maxim de apa rece:

Qomax= Kox Qzimax/10 =2.2x39.75/10 = 8.75mc/h

unde : Kzi- coef. de variatie zilnica a debitului =1,15

Ko- coef. de variatie orara a debitului =2.2

Kp- coef. de pierderi pe retea =1,08

n - numarul de ore de functionare zilnic =10

N - numarul de persoane

qs - norma de apa pe persoana si zi

Calculul volumului rezervorului pentru consum menajer si de incendiu interior

Volumul intangibil de incendiu interior

Vi = 1/1.000 (2.5 l/s x 3.600 s x 0.17 h ) = 1.60 mc

Vrez = Vcmp + Vi unde V cmp = volumul de compensare pentru aplatizarea curbei de consum apa menajera in orele de varf;

Vcmp = aQzi max = 0,25 x (39.75+14.40)mc/zi 13.54mc.

Vrez = 13.54 +1.60 mc = 15mc.

Rezervorul existent cu debitul de 15 mc, montat in statia de pompare din corpul "C"este suficient pentru a asigura rezerva intangibila de incendiu interior si consum menajer.

EXECUTIE, RECEPTIE, PROBE

Executia, receptia si exploatarea instalatiilor interioare si exterioare de alimentare cu apa se va face conform :

- Normativ I9/1994

- Normativ I9/1-1996

In timpul executiei instalatiilor exterioare de alimentare cu apa, instalatorul va folosi indicatoarele de securitate conform STAS 297/1 si STAS 297/2.

Montajul , exploatrea si intretinerea echipamentelor se va face in stricta conformitate cu instructiunile si cartile tehnice ale furnizorilor lor.

Pe parcursul executiei instalatiilor de apa rece, conform normativului I 9 cap. 13 (art. 13.1 ÷ 13.8), executantul va efectua urmatoarele incercari:

pentru conductele de alimentare cu apa rece:

- incercarea de etanseitate la presiune la rece;

- incercarea de functionare;

Presiunea de incercare la etanseitate si la cald la conductele de apa rece va fi 1,5 x presiunea de regim (4 bar x 1,5 = 6 bar), timp de 20 minute, fara sa existe scaderi de presiune.

Incercarea de functionare avand echipamentele in functiune (pompe, hidrofoare)

Toate probele se vor efectua in prezenta reprezentantului beneficiarului, rezultatele acestora consemnandu-se in procese - verbale.

RECEPTIA LUCRARILOR

Receptia lucarilor de executie se va face conform:

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  Normativului C56/02

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  Legii nr. 10/1995

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  Regulamentului de receptie a lucrarilor de constructii aprobat cu HGR nr 273 / 1994

In toata perioada existentei instalatiilor, exploatarea si intretinerea acestora se va face corespunzator cerintelor din Normativul I9 / 1 - 96.

MODUL DE URMARIRE IN TIMP A LUCRARILOR DE INSTALATII DE ALIMENTARE CU APA SI DE CANALIZARE

a ) Instalatii interioare de alimentare cu apa si canalizare

Urmarirea in timp a instalatiilor se face pe intreaga perioada de utilizare a acestora.

In primii 3 ani instalatiile se verifica la perioade mai scurte (1 luna) pentru depistarea defectelor determinate de defectiuni de fabricatie si executie nedepistate la probele si receptiile finale .

Verificarea instalatiilor se face prin urmarirea in special a:

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  imbinarilor instalatiei de alimentare cu apa;

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  mobilitatii de manevrare a vanelor principale;

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  presiunii de lucru a instalatiei de alimentare cu apa;

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  etanseitatii imbinarilor tuburilor de canalizare montate in ghene.

Verificarea instalatiilor are un caracter permanent dupa perioada de rodaj a instalatiilor, verificari care duc la:

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  controlul si verificarea instalatiei pentru asigurarea functionarii in regim normal;

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  revizia instalatiei (anual);

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  reparatii curente (lunar);

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  reparatii capitale;

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  reparatii accidentale.

Programul de verificare a functionarii in timp a instalatiilor se intocmeste de beneficiar (administrator) tinand seama de indicatiile proiectantului si a proceselor verbale de receptie a lucrarilor.

b) Racorduri de alimentare cu apa si canal aferente cladirii la retelele de apa si canal in zona

Verificarea in timp a instalatiilor de apa ce apartin cladirii constau in urmarirea:

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  functionarii alimentarii cu apa prin apometru;

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  eventualele pierderi de apa in sol sau canale de protectie;

-   &nbs 24124p1514y p;   &nbs 24124p1514y p;  starii de functionare a caminului de racord.

Verificarea in timp a functionarii instalatiilor de apa interioare se face de catre personal calificat in domeniul ce are in dotare scule si echipamente adecvate.

7. MASURI DE PROTECTIA MUNCII SI PSI

La executia si exploatarea instalatiilor sanitare interioare se vor respecta :

Normele generale de protectia muncii - 1996 ;

Normele specifice de securitate a muncii pentru instalatiile tehnico-sanitare si de incalzire - 1996/cod 28 - avizat de MMPS ;

Regulamentul privind protectia si igiena muncii in constructii - aprobat de MLPAT cu ord. nr. 9N/1993 ;

Normativ C300

9. DOTARI DE PRIMA INTERVENTIE:

Prevederea mijloacelor de prima interventie se va efectua in baza urmatoarelor norme specifice:

- Normativul de siguranta la foc a constructiilor, indicativ P 118 - 99, Cap. 3, art. 3.10.1;

- Ordinul Ministerului de Interne pentru aprobarea "Dispozitiilor generale privind echiparea si dotarea constructiilor, instalatiilor tehnologice si a platformelor amenajate cu mijloace tehnice de prevenire si stingere a incendiilor" - D.G.P.S.I. - 003 din 2001

Stabilirea numarului de stingatoare portative si tip de agent de stingere pentru contructia civila (publica) se va efectua functie de destinatiile spatiilor, asigurade-se dotarea cu cate un stingator portativ cu pulbere de 6 kg sau echivalentul acestuia pentru o arie construita de maximum 250 m2, dar minimum doua stingatoare pe fiecare nivel al cladirii.

INTOCMIT, 


Document Info


Accesari: 6886
Apreciat: hand-up

Comenteaza documentul:

Nu esti inregistrat
Trebuie sa fii utilizator inregistrat pentru a putea comenta


Creaza cont nou

A fost util?

Daca documentul a fost util si crezi ca merita
sa adaugi un link catre el la tine in site


in pagina web a site-ului tau.




eCoduri.com - coduri postale, contabile, CAEN sau bancare

Politica de confidentialitate | Termenii si conditii de utilizare




Copyright © Contact (SCRIGROUP Int. 2024 )